Rack Installation
Use the following procedures to install the equipment in a 23- or 19-inch equipment rack.
The procedures provided in this section assume all the components to be installed are being ordered from Tellabs®. If any component was not ordered from Tellabs®, refer to the installation instructions included with that component.
|
Warning: The equipment in the following procedures shall be installed in a restricted access location from the general public. Only trained personnel shall be allowed access to perform maintenance functions after the equipment is installed and energized. |
The components required for the installation of each shelf are listed in the following table.
Table 1: 1150 MDS5 Required Components
| Shelf | Description | Qty Req’d |
| Tellabs 1150 MDS5 | 19-Inch DC Rectifier Shelf w/Extension Mounting Brackets | 1 |
| 40 Amp Circuit Breakers (shelf) | 2 | |
| 7.5 Amp GMT Fuses (fan tray) | 4 | |
| AC Power Cables | 2 | |
| MDS5 Shelf | 1 | |
| MDS5 Power Cable | 1 | |
| MDS5 Digital Ground Cable | 1 | |
| 23-Inch Fan Tray w/Mounting Brackets | 2 | |
| 23-Inch Fan Tray Power and Alarm Cable Assy | 2 |
Table 2: 1150E MDS7 Required Components
| Shelf | Description | Qty Req’d |
| Tellabs 1150E MDS7 | 19-Inch DC Rectifier Shelf w/Mounting Brackets | 1 |
| 40 Amp Circuit Breakers provided, 30 Amp min required (shelf) | 2 | |
| 7.5 Amp GMT Fuses (fan tray) | 4 | |
| AC Power Cables | 2 | |
| MDS7 Shelf | 1 | |
| MDS7 Power Cable | 1 | |
| MDS7 Digital Ground Cable | 1 | |
| MDS7 Fan Tray Alarm "Y" Cable | 1 | |
| 19-Inch Fan Tray w/Mounting Brackets | 2 | |
| 19-Inch Fan Tray Power and Alarm Cable Assy | 2 | |
| Note: If installing the MDS7 with 19-Inch Fan Trays in a 23-Inch Rack, additional mounting bracket extensions are required. | ||